www.svri.nl Open in urlscan Pro
185.37.70.66  Public Scan

URL: https://www.svri.nl/en/selecting-a-current-transformer-ct/
Submission: On April 18 via manual from US — Scanned from NL

Form analysis 1 forms found in the DOM

GET https://www.svri.nl/en/

<form method="get" class="searchform search-form" action="https://www.svri.nl/en/" role="search"><input type="text" value="Search this website …" name="s" class="s search-input" onfocus="if ('Search this website …' === this.value) {this.value = '';}"
    onblur="if ('' === this.value) {this.value = 'Search this website …';}"><input type="submit" class="searchsubmit search-submit" value="Search"></form>

Text Content

COOKIES ARE USED ON THIS WEBSITE. - CHANGE YOUR SETTINGS

 * Strictly necessary Some cookies on this website are strictly necessary and
   cannot be disabled.

Cookie Consent plugin for the EU cookie law
 * Close
 * Allow for all sites



https://www.svri.nl/en/selecting-a-current-transformer-ct/

18 April 2022

nl | en Posts

Hans Stutvoet MSc

Electrical Engineer, Power Systems Consultant, Owner of SVRI bv

SEARCH


 * Home
 * Engineering & Consultancy
 * Training Courses
 * SKM Power Tools »
   * Products
   * Prices & Quotations
   * Service & Support
 * About.. »
   * Hans Stutvoet
   * SVRI
   * SKM Systems Analysis
 * Links


SELECTING A CURRENT TRANSFORMER (CT)



If the current ratio, burden and class are selected, the current transformer
(CT) has been specified basically. Of course additional
requirements like type, frequency, isolation level, maximal short circuit
current and environmental conditions should also be specified.

 


CURRENT RATIO IP/IS

The current ratio is the ratio between the primary and  secondary current.

For the primary current Ip you can select the first value that
follows the highest continuous current from the range:
1 – 1.25 – 1.5 – 2 – 2.5 – 3 – 4 – 5 – 6 – 7.5 A

Decades also belong to the range, like for example:
1000 – 1250 – 1500 – 2000 – 2500 – 3000 – 4000 – 5000 – 6000 – 7500 A

The secondary current Is is mostly 1A or 5A.
– 1A is my favorite, because the cable losses verliezen (VA) are 25x less
compared with 5A.
– 1A current transformer could be smaller at a required knee-point voltage.
– 5A was required when relays took their power supply from the sensing current.
– 5A is still commonly used in the US, unfortunately.

 


ACCURACY

The accuracy of a current transformer depends among others of :
– burden
– class/saturation
– load
– frequency
– temperature


ACCURACY BASED ON BURDEN AND CLASS (IEC)

For the burden you can select the first value that follows the actual load
(including cable losses) from the range:
2.5 – 5 – 10 – 15 – 30 VA

For the class you can select:

Application Class Very accurate metering  0.1 – 0.2 Tariff (kWh) metering  0.5 –
0.5S – 0.2 – 0.2S Instrument meters and control 1 Protection (P) 5P20 – 5P10 –
10P10

 

Sometimes the factor of security (FS) is also specified to protect metering
devices against high short circuit currents. If FS = 5, the composite error at 5
x Ip ≥ 10%. Standard values are:
FS 5 – FS 10


ACCURACY BASED ON KNEE-POINT VOLTAGE AND RCT

For class X (BS), and class PX and PR (IEC) current transformer for
protection relays the accuray is not based on burden and class, but on:
– minimum knee-point voltage, with corresponding maximum magnetising current
– secondary winding resistance Rct (75°C)
– load

Note: IEC and ANSI/IEEE define knee-point voltage different


ACCURACY BASED ON ANSI/IEEE STANDARDS

For current transformers for metering you should select a burden in ohms and an
accuracy percentage. A B0.5 is a 0.5 ohm load, For example.
Burden: B0.1 – B0.2 – B0.5 – B0.9 – B1.8
Accuracy percentage: 0.3 – 0.6 – 0.9 – 1.2 – 2.4

For current transformers for protection there is a C-range, that is given in the
tabel with the IEC equivalent.

ANSI/IEEE IEC (5 A CTs) C100 25VA, 5P20 C200 50VA, 5P20 C400 100VA, 5P20 C800
200VA, 5P20

 
Notes:
– C400 and C800 can be very large CTs
– Divide burden (VA) by 5 for 1 A CTs

 


EXAMPLES AND TIPS

 * If the maximum continuous current is 1124 A (50 Hz), then the current
   transformer specification for protection could be: 1250/1 A, 10 VA, 5P20
 * For kWh metering could be: 1250/1 A, 5 VA, cl. 0.2S
 * Or with a factor of security: 1250/1 A, 5 VA, cl. 0.2S FS 5
 * The accuracy class is only applicable if the total load including cable
   losses is approximately equal to the current transformer burden.
 * If the burden of a current transformer for metering is much higher than the
   load, instruments and devices could be damaged if short circuit occurs
   somewhere.
 * A current transformer could comply with requirements of several combinations,
   e.g. 30 VA, 5P10 and 15 VA, 5P20.
 * For metering the ANSI/IEEE specification of the current transformer could
   be 500/5A, 0.3 B0.5 (, 60 Hz). In that case, the burden will be 0.5 x 5² =
   12.5 VA.
 * For protection the ANSI/IEEE specification of the current transformer could
   be 500/5A C100 (, 60 Hz). The secondary current through a standaard 1 ohm
   load can be 20 × 5 A = 100 A , with an inaccuracy less than 10%. The
   voltage over the load will be 100 V.

 


SEE ALSO

 * Wikipedia – Current transformer
 * RS Isolsec – Selecting a Current Transformer

 


REFERENCES

 * IEC 61869-1 – Instrument transformers – Part 1: General requirements
 * IEC 61869-2 – Instrument transformers – Part 2: Additional requirements for
   current transformers
 * IEC 60044-1 and IEC 185 are withdrawn current transformer standards
 * IEEE Std C57.13-2008 – IEEE Standard Requirements for Instrument Transformers

 * 
 * 
 * 
 * 
 * 
 * 

Filed Under: Generators, Power Systems, Protection

DIRECT CONTACT

Hans Stutvoet MSc
Power Systems Consultant at
SVRI Electrical Engineering
Rotterdam Area, Netherlands
T +31 622992403
E info@svri.nl


SUBJECT

 * Generators
 * Power System Analysis
 * Power Systems
 * Protection
 * SKM Power Tools (PTW)
 * Voltage Control

TAGS

abb alstom arc flash basler beckwith brush cable cee droop gec ge energy ge
multilin harmonics IED internet isochronous load flow power management system
protective relay ptw rail conductor system schneider short-circuit analysis skm
power tools speed control standards svri switchgear transformer voltage
regulator

Return to top of page

 * General Terms And Conditions
 * Privacy & Cookies Policy

Copyright © 2022