www.ascopower.com Open in urlscan Pro
2a02:26f0:480:597::37b2  Public Scan

Submitted URL: https://email.btobinnovate.com/c/14dMbRPDr9XiJ9Pm8E6yjy8jQigHg
Effective URL: https://www.ascopower.com/us/en/resources/technical-briefs/three-reasons-to-choose-ul-1008.jsp?utm_source=marketo&utm_medi...
Submission: On January 17 via api from US — Scanned from DE

Form analysis 1 forms found in the DOM

GET https://www.ascopower.com/us/en/search/

<form id="search-bar" class="search-bar__form" method="get" action="https://www.ascopower.com/us/en/search/" novalidate="">
  <div class="search-bar__input-container">
    <div class="search-bar__magnifying-glass">
      <svg xmlns="https://www.w3.org/2000/svg" viewBox="0 0 1024 1024">
        <path
          d="M831 801c8 8 8 22 0 30-4 4-10 6-15 6-6 0-11-2-15-6L645 675c-49 42-112 67-181 67-153 0-277-125-277-278s124-277 277-277 278 124 278 277c0 69-25 132-67 181zM230 464c0 130 105 235 234 235 64 0 121-25 164-66 0-1 1-2 2-3s2-2 3-2c41-43 66-100 66-164 0-129-105-234-235-234-129 0-234 105-234 234zm234-192c12 0 22 10 22 22 0 11-10 21-22 21-82 0-149 67-149 149 0 12-10 22-21 22-12 0-22-10-22-22 0-106 86-192 192-192z">
        </path>
      </svg>
    </div>
    <input type="search" name="q" class="search-bar__input" placeholder="Search products, documents &amp; more" required="" autocomplete="off">
    <button type="reset" name="reset" id="uiaas-search__search-bar-reset-button" class="search-bar__reset-button" value="Search" aria-label="Search">
      <svg xmlns="https://www.w3.org/2000/svg" viewBox="0 0 1024 1024">
        <path d="M590.3,512l290.2,290.2c20.5,20.5,20.5,56.5,0,77.1c-12.8,10.3-25.7,15.4-38.5,15.4c-15.4,0-28.3-5.1-41.1-15.4L513.3,589.1
                                                              	L223,879.3c-12.8,10.3-25.7,15.4-38.5,15.4c-15.4,0-28.3-5.1-41.1-15.4c-20.5-20.5-20.5-56.5,0-77.1L433.7,512L143.4,221.8
                                                              	c-20.5-20.5-20.5-56.5,0-77.1c23.1-20.5,56.5-20.5,79.6,0l290.2,287.7L801,144.7c23.1-20.5,56.5-20.5,79.6,0
                                                              	c20.5,20.5,20.5,56.5,0,77.1L590.3,512z"></path>
      </svg>
    </button>
  </div>
  <button type="submit" name="submit" id="submit" class="search-bar__button" title="" value="Search">
    <svg xmlns="https://www.w3.org/2000/svg" viewBox="0 0 1024 1024">
      <path
        d="M831 801c8 8 8 22 0 30-4 4-10 6-15 6-6 0-11-2-15-6L645 675c-49 42-112 67-181 67-153 0-277-125-277-278s124-277 277-277 278 124 278 277c0 69-25 132-67 181zM230 464c0 130 105 235 234 235 64 0 121-25 164-66 0-1 1-2 2-3s2-2 3-2c41-43 66-100 66-164 0-129-105-234-235-234-129 0-234 105-234 234zm234-192c12 0 22 10 22 22 0 11-10 21-22 21-82 0-149 67-149 149 0 12-10 22-21 22-12 0-22-10-22-22 0-106 86-192 192-192z">
      </path>
    </svg>
  </button>
</form>

Text Content

Skip To Main Content
USA Our Brands
Item count in cart is 0 My Documents Partner Portal
User name


Our Brands

 * Products
   
 * Solutions
   
 * Services & Support
   
 * Resources
   
 * About Us
   

USA Our Brands My Documents 0 Partner Portal
User name





Welcome to the ASCO Website

Welcome to our website.
Stay on this website Choose another country or region


 * Resources
 * Technical Briefs

 * Three Reasons to Choose UL 1008 Transfer Switches


THREE REASONS TO CHOOSE UL 1008 TRANSFER SWITCHES


Transfer switches are critical to powering life-safety and legally required
systems as well as mission-critical loads. UL1008 – Standard for Safety –
Transfer Switch Equipment specifies the safety and endurance tests for verifying
that transfer switches offer the highest levels of reliability and power
availability. This article highlights important aspects of UL 1008 testing.

Highlights of UL 1008 Electrical Testing

Because a transfer switch is always connected to a power source, it must be
capable of carrying its rated amount of current continuously. When faults occur,
a transfer switch must carry the resulting current until it is cleared by a
circuit breaker or fuse. If a transfer switch instead opened when faults
occurred, it would leave loads without power even when power is restored to the
facility. For the same reason, a transfer switch must also be able to reliably
close on fault currents.

Manufacturers design generator transfer switches to provide specific service and
fault current capabilities. To verify them, UL 1008 tests the ability of
transfer switches to withstand and close on fault currents. The procedures
required to verify corresponding ratings and functionality under fault
conditions include the Withstand Test, the Closing Test, and the Dielectric
Voltage Withstand Test.

Withstand Test

A transfer switch with closed main contacts is subjected to a short-circuit
current of 20 to 50 times its service rating. More specifically, switches rated
up to 100, up to 400, and greater than 400 Amps must respectively withstand
minimum currents of 5,000 Amps, 10,000 Amps, and current at least 20 times the
nominal switch ampacity (but not less than 10,000 Amps) until the current is
cleared by an upstream fuse or breaker. The power factor must not exceed 0.50
for currents up to 10,000 Amps, 0.30 for currents up to 20,000 Amps, and 0.20
for currents exceeding 20,000 Amps.

Closing Test

Transfer switches must also be able to close on fault currents until cleared by
an upstream protective device. Consequently, the withstand test is repeated,
this time starting with the main contacts open. During this test, the contacts
must close on and withstand a current with the same electrical parameters used
for the Withstand Test.

Dielectric Voltage Withstand Test

Following these tests, an ac current of twice the rated voltage (but not less
than 900V) must be applied to a transfer switch while voltage is measured at six
types of locations within the device.

Passing Criteria

The switch must present the following conditions when the tests are complete:
• ability to close on untested contacts of the opposite power source circuit
• operability using whatever automatic or manual controls are provided
• no continuity between the terminals of the normal and alternate power source
circuits
• no opening of doors on transfer switch enclosures
• cables cannot pull away from lugs and connectors

Optional Short-Time Tests

The aforementioned electrical tests require switches to carry a fault current
until cleared by a protective device. However, many facilities employ selective
coordination schemes using breakers that must withstand fault currents for
specific durations. UL 1008 gives equipment manufacturers the option of
demonstrating that a transfer switch can withstand and close on currents for
times ranging from 0.1 to 0.5 seconds. If successful, manufacturers can mark a
switch with corresponding Short-Time Ratings.

For more information about UL 1008 electrical rating tests, review the ASCO
Power Technologies document entitled UL 1008 Transfer Switch Withstand and
Closing Ratings. ASCO’s Selective Coordination Basics provides insight into
coordinating overcurrent protection devices to minimize the scope of outages.

Performance Tests

Tests with profound implications for switch safety and longevity include the
Overload Test, Endurance Test, and Temperature Rise Test.

Overload Test

An overload test of a transfer switch requires cycling electrical load between
power sources while the switch carries the overcurrents prescribed in Table 1.
According to switch ampacity, it must carry these currents for the quantities of
cycles listed in Table 2.


Using the values in the tables, a nominally rated 800 Amp ac transfer switch
serving Total System Loads must be subject to 4800 Amps at a power factor
between 0.4 and 0.5 for 50 operating cycles at a rate of one cycle every 4
minutes.

Temperature Rise Test

Following overload testing, coils and heating elements in the switch are
energized while the transfer switch carries 100 percent of its rated load until
temperatures in the device equilibrate. The resulting temperatures are then
compared to maximum temperature criteria for more than a dozen types of
components and insulating materials specified by UL 1008.

Endurance Test

Endurance tests involve operating transfer switches with (and sometimes without)
current at specified power factors. They must carry specified amounts of load
for the quantities of cycles shown in Table 3.

If the manufacturer wishes to mark the switch for use with only “Optional
Loads”, then the reduced quantities of cycles shown in Table 4 may be used. Such
switches cannot be used for life-safety or legally required loads.

Passing Criteria

If a switch passes the Temperature Rise Test, the endurance tests do not result
in evidence of mechanical or electrical dysfunction, and the switch passes a
subsequent Dielectric Voltage Withstand Test, it will have satisfied UL1008
requirements for performance. For additional information regarding UL 1008
performance tests, review the ASCO Power Technologies’ document entitled
Performance Testing for Transfer Switches.

Significance of UL 1008 Tests

The UL 1008 standard specifies rigorous testing requirements for transfer switch
equipment. Three resulting benefits of using an UL 1008-Listed transfer switch
include:

1. Withstand and closing tests that place severe stresses on the transfer switch
2. Endurance testing the surpasses the operating conditions that most transfer
switches will ever see
3. The assurance that comes with subjecting an entire transfer switch device,
and not just a subset of its components, to severe conditions

As a result, the UL 1008 standard reflects safety, reliability, and performance
standards that are necessarily severe for devices that will be used to power
life-safety and critical loads. Here’s why.

In the earlier example, an 800 Amp ac switch serving Total System Loads required
overload testing at 4800 Amps and a power factor between 0.4 and 0.5 for 50
operations at four cycles per minute. Likewise, the Endurance Test for the same
switch requires 1000 cycles without current and 2000 cycles with current, with
half of those operations at 200 percent of rated current.

These parameters far exceed the conditions that most facilities will ever see.
It is worth noting that all of the tests are executed using a complete transfer
switch, including its transfer mechanism, controls, components, wiring, and
enclosure. The extent and severity of testing required for a UL 1008 listing
verifies that transfer switches can withstand switching duty under the most
severe conditions and reliably provide many years of service.

References

Underwriters Laboratories. UL 1008 - Standard for Safety – Transfer Switch
Equipment. 2014.

ASCO Power Technologies, Inc. UL 1008 Transfer Switch Withstand and Closing
Ratings. 2019.

ASCO Power Technologies, Inc. Selective Coordination Basics. 2018.

ASCO Power Technologies, Inc. Performance Testing for Transfer Switches. 2020

Ooooooops! EROOR! Internal error occurred! java.io.FileNotFoundException:
/app/tomcat/asco/Corp-asco/apache-tomcat-9.0.68/webapps/ROOT/WEB-INF/Views/SE_v2/HBS/ContentStickyBar/template.page.hbs
AbstractEntityModel(id=94027-101535, xpmPropertyMetadata={})
Ooooooops! EROOR! Internal error occurred! java.io.FileNotFoundException:
/app/tomcat/asco/Corp-asco/apache-tomcat-9.0.68/webapps/ROOT/WEB-INF/Views/SE_v2/HBS/ApplicationSocialMediaShareVertical/template.page.hbs
AbstractEntityModel(id=70971-101513, xpmPropertyMetadata={})

Accessibility mode off Accessibility mode on


ABOUT US

Company Profile Connect with us Privacy Policy Accessibility

SUPPORT

Contact Support Find a Document Find a Product

CONTACT US

Contact Sales Contact Support Contact Corporate Subscribe

QUICK LINKS

Our Products Find a drawing White Papers Articles News Releases Digital Binders

Privacy Policy Terms of use Change your cookie settings Subscribe
©2024, ASCO Power Technologies




Support Center Support Center


COOKIES AND PRIVACY

Our website uses cookies delivered by us and by third parties. Some cookies are
necessary for the website’s operation, while others can be adjusted by you at
any time, in particular those which enable us to understand the performance of
our website, provide you with social media features, and deliver a better
experience with relevant content and advertising. By your usage of this site you
accept all cookies, or you may

Reject All Accept All
Change your cookie settings



PRIVACY SETTINGS

When you visit any website, it may store or retrieve information on your
browser, mostly in the form of cookies. This information might be about you,
your preferences or your device and is mostly used to make the site work as you
expect it to. The information does not usually directly identify you, but it can
give you a more personalized web experience. Because we respect your right to
privacy, you can choose not to allow some types of cookies. Click on the
different category headings to find out more and change our default settings.
However, blocking some types of cookies may impact your experience of the site
and the services we are able to offer.
More Information
Allow All


MANAGE CONSENT PREFERENCES

NECESSARY COOKIES

Always Active

Necessary cookies are required for our website to work properly and can’t be
turned off. They are sent to your computer or device when you request a specific
action or service, e.g. when you log in, fill out a form, or set your cookie
preferences. If you set your browser to block or alert you about these cookies,
certain parts of our website won’t work.

CUSTOMIZATION COOKIES

Customization cookies

Customization cookies allow you to configure our website to your preferences
(e.g. language, region) and enable enhanced functionalities. They are delivered
by us or by other companies. If you don’t accept them, we won’t be able to save
your preferences and some services on our website may not be available.

STATISTICAL COOKIES

Statistical cookies

Thanks to statistical or analytical cookies, delivered by us and other
companies, we can count the visits on our website and know the sources of
traffic. The data we derive helps us understand what visitors like most and
improve the website. If you don’t accept them, we won’t be able to improve your
experience based on data from your visit.

MARKETING COOKIES

Marketing cookies

Marketing cookies on our website are delivered by other companies and used to
identify your interests and display relevant advertising content when you browse
outside of our website. These cookies can enable social media features such as
sharing and simplifying registration. If you do not accept them, you will still